If the motor deceleration by the mechanical brake causes extra heat
generation in the Ex zone, make sure that the use of the brake does
not increase the temperature too much.
In some cases you cannot use the brake for the motor deceleration
when the motor thermal protection circuit has tripped and the motor
temperature is too high.
For more information, see the drive firmware manual (or the FSO
module user’s manual if you use the Safe brake control (SBC) function
of the FSO module).
Parameter settings 63