Displays the status of FPTC modules. The
word can be used as the source of eg. ex-
ternal events. This parameter is read-only.
FPTC status word35.04
DescriptionNameBit
1 = Yes: An FPTC module has been detec-
ted in slot 1.
Module found
in slot 1
0
1 = Yes: The module in slot 1 has an active
SMT fault.
Fault active in
slot 1
1
1 = Yes: The module in slot 1 has an active
motor temperature warning.
Warning active
in slot 1
2
1 = Yes: An FPTC module has been detec-
ted in slot 2.
Module found
in slot 2
3
1 = Yes: The module in slot 2 has an active
SMT fault.
Fault active in
slot 2
4
1 = Yes: The module in slot 2 has an active
motor temperature warning.
Warning active
in slot 2
5
1 = Yes: An FPTC module has been detec-
ted in slot 3.
Module found
in slot 3
6
1 = Yes: The module in slot 3 has an active
SMT fault.
Fault active in
slot 3
7
1 = Yes: The module in slot 3 has an active
motor temperature warning.
Warning active
in slot 3
8
Reserved9…15
Contains hardware-related settings that can
be enabled and disabled by toggling the
specific bits.
Special HW settings95.15
DescriptionNameBit
1 = The driven motor is an Ex motor
provided by ABB for potentially explosive
atmospheres. This sets the required minim-
um switching frequency for ABB Ex motors.
EX motor0
For non-ABB Ex motors, contact your local
ABB representative.
Switching frequency limitation
The certificate of the Ex motor typically requires that you set a
minimum limit for the switching frequency of the drive.
52 Parameter settings