EasyManua.ls Logo

ABB LVS Digital FC610 - Figure 10: FC610 Basic Unit Top View Terminal Layout

ABB LVS Digital FC610
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WIRING CONNECTIONS PROD UCT IN FORMATI ON
1TNC9 2825 0M0201 12
Figure 10: FC610 basic unit top view terminal layout
Terminal name
Function
Description
L, N
Power supply
110-240 VAC
R0a, R0b
Relay output
24 to 110 VDC, 110 to 240 VAC
DI0...DI1
Digital inputs
24 VDC
OUT/L+, OUT/M
DC power output
24 VDC*
A, B, FE
RS485 interface
For Modbus RTU connection; FE shield terminal
VL1, VL2, VL3, VN
Voltage inputs
L1, L2, L3
Current Measurement
MP
Interface of MP53/56
RJ12 socket
*) FC610 provides 24 VDC output with a max load of 100 mA @ 240 VAC of power supply or 50 mA @
110 VAC of power supply.