WIRING CONNECTIONS PROD UCT IN FORMATI ON
1TNC9 2825 0M0201 13
2.5.2 Wiring connections
FC610 generates a 24 VDC output internally for digital inputs. The maximum load of the inter-
nal supply is 100mA@240 VAC input or 50mA @ 110 VAC input of power supply.
Figure 11: 24 VDC power output
One relay output is available for general fault indication by default. The relay is rated
2A@240VAC AC-15. Please refer to Appendix A Technical data” for more details.
Figure 12: Relay output connection
The R0 relay output is pre-configured as ‘common warning’ function.
There are two sets of digital inputs available and pre-configured as main switching device
status (DI0) and fault (DI1) indication with ‘NO’ input characteristics.
The digital inputs can be supplied directly from internal 24 VDC power output.
Figure 13: DIs supplied by internal 24 VDC