CONFIGUR AT ION PAGES H MI MP53/MP 56
1TNC9 2825 0M0201 44
4.4.3 Supervision functions setting
Supervision functions including power quality supervision and load supervision are,
Over current supervision, current unbalance supervision, voltage unbalance supervision, volt-
age dip supervision, voltage swell supervision, voltage interruption supervision and phase
sequence supervision.
Level 1
Level 2
Level 3
Value range
(PARA: Parameters)
(I-OS: Over
Current
Supervision)
(FUNC: Function)
/
(Disable/Enable)
(THSH: Threshold)
100 %-120 %
(HYST: Hysteresis)
0 %-10 %
(I-US: Current
Unbalance
Supervision)
(FUNC: Function)
/
(Disable/Enable)
(THSH: Threshold)
50 %-90 %
(HYST: Hysteresis)
0 %-10 %
(U-US: Voltage
Unbalance
Supervision)
(FUNC: Function)
/
(Disable/Enable)
(THSH: Threshold)
50%-90%
(HYST: Hysteresis)
0%-10%
(U-DS: Voltage Dip
Supervision)
(FUNC: Function)
/
(Disable/Enable)
(THSH: Threshold)
5 %-100 %
(HYST: Hysteresis)
0 %-10 %
(U-SS: Voltage
Swell Supervision)
(FUNC: Function)
/
(Disable/Enable)
(THSH: Threshold)
5 %-20 %
(HYST: Hysteresis)
0 %-10 %