A .1 T ECHN ICAL SPECI FICAT IONS CONFIG URAT ION
1TNC9 2825 0M0201 50
Appendix A Technical Data
A.1 Technical specifications
Main circuit
Nominal voltage
3 X 230/400 VAC (Ph/N)
Voltage range
3 X 30 – 400 VAC (Ph/N)
Rated insulation voltage
800 VAC
Frequency
50 or 60 Hz (45 – 65 Hz)
Voltage inputs
Voltage between phases
50 – 690 VAC
Voltage between phase and neutral
30 – 400 VAC
Input consumption
0.3VA max.
Updating duration
1s (on MP53/56 HMI)
0.1s (via bus)
Terminal wire area
0.2 .. 2.5 mm
2
Recommended tightening torque
0.5 .. 0.6 Nm
Current inputs
Primary current via CT
Up to 10000 A
Rated current In
1 A / 5 A
Maximum linear current I
max
6 A
Minimum current I
min
10 mA with U(Ph/N) > 29 VAC
Updating duration
1s (on MP53/56 HMI)
0.1s (via bus)
General data
PMD classification
PMD SD K55
Housing color- FC610 basic unit
RAL7012
Housing color- HMI
RAL7012
HMI Display
LCD
Material- FC610 basic unit
PA6 GF20
Halogen-free
Flammability rating UL94V2
Pollution degree
2