NCC connection with two IEC 104 LAN communications including 116 IEDs
resulting in 2 800 process updates per second sent to two NCCs
*)
90% 16-bit analog data without time, 5% binary data without time and 5% binary data
with time
The following list shows some examples when IEDs are connected to SYS 600C with
Local process database and displayed with Workplaces:
60 IEDs with IEC 61850 protocol and 1 Workplace with 1 050 display objects
63 IEDs with IEC 61850 protocol and 2 Workplaces both including 450 display
objects
77 IEDs with IEC 61850 protocol and 1 Workplace including 150 display objects