PGS100 AND PAS100 | PRESSURE TRANSMITTERS | OI/PGS/PAS100-EN REV. A
...4 Mounting
Measuring pipe
In order for the pipes to be laid correctly, the following points must be observed:
Keep the measuring pipe as short as possible and avoid sharp bends.
Lay the measuring pipe in such a way that no deposits can accumulate in it. Gradients should not be less than approx. 8 %
(ascending or descending).
The measuring pipe should be blown through with compressed air or, better yet, flushed through with the measuring medium
before connection.
Completely depressurize the measuring pipe if the medium is a fluid.
Lay the measuring pipe in such a way that gas bubbles (when measuring fluids) or condensate (when measuring gases) can
flow back into the process line.
When measuring steam, lay the measuring pipe in such a way that hot steam cannot flow back into the process connection
(water trap, e.g., a water trap pipe that is filled with water before installation).
Check the tightness of the connection.