12 | © 2022 ABB | - 1SDH002203A1002 RS-485 serial communication interface (COM1 port)
The next diagram illustrates an RS-485 network with Master device at the end of the serial line.
1. E-kit Master at the end of the bus line, pull-ups and pull-downs activated, bus termination with 120
Ω resistors
2. Slave in the serial line.
3. Slave at the end of the serial line, termination with 120 Ω resistors
There is no need for a termination resistor if the Master device is in the serial line. However, the pull-up and
pull-down resistors must be activated (see next diagram).
1. Slave at end of serial line, termination with 120 Ω resistors
2. E-kit Master at end of serial line, pull-ups and pull-downs activated
3. Slave in the serial line
4. Slave at the end of the serial line, termination with 120 Ω resistors
The following photo illustrates the COM1 terminal box of E-kit when it is inside the serial line.