25 | © 2022 ABB | - 1SDH002203A1002
ABB | E-kit
Web interface configuration
A channel is enabled by selecting the corresponding Yes button: all the parameters that can be configured
will now appear. The editable parameters are listed below:
1. Target: type of channel
Note: the Logic type is reserved for future use;
2. Enabling of value validity control (Check Not Valid Value option). If the value is not valid, the default
value will appear on a level with the value itself.
3. If the Check not valid option is enabled, the default value will appear in Not Valid Value if the value
is not valid;
4. Access: type of access to the data item (read or write)
5. Addressing: type of data item addressing;
6. Address: the data address is entered;
7. Modbus Type: type of data item;
8. Modbus Bit (only with Modbus Type = bool) specific bit;
9. Normalization bit mask: mask for annulling the unwanted bits. The format managed is Hexadecimal;
the mask entered must have this form: ‘16# (…) followed by the content expressed in hex. For example,
if only the first two bits of a register must be considered, ‘16# 3’; would have to be indicated within
this field;
10. Normalization bit shift: shifts the bits to the right or left by as many positions as the configured value;
11. Normalization numerator: scales the value by multiplying it by the indicated number;
12. Normalization denominator: scales the value by dividing it by the indicated number;
13. Normalization offset: adds an offset to the data item. The value set can be both positive and negative