14
5. Connect the Kocos to the breaker contacts/bus:
5. If the result is different from the suggested range of 0.157 in 0.177 in (4.0 mm 4.5 mm),
turn the pushrod’s end clockwise to increase wipe, or counter-clockwise to decrease wipe,
depending on the adjustment needed to achieve a measurement within the specified range.