6.3 Breaker Ready / Not Ready Binary Output Contacts and Ready
Light Status
CONDITION
CIRCUIT BREAKER POSITION
CLOSE
OPEN
Capacitor Energy sufficient For O-
CO operations
Ready LED: on
Ready contact: closed
Not ready contact: opened
Ready LED: on
Ready contact: closed
Not ready contact: opened
Capacitor Energy sufficient for CO
operations
Ready LED: blinking
Ready contact: closed
Not ready contact: opened
Ready LED: blinking
Ready contact: closed
Not ready contact: opened
Capacitor Energy sufficient for O
operations
Ready LED: blinking
Ready contact: closed
Not ready contact: opened
Ready LED: off
Ready contact: opened
Not ready contact: closed
Capacitor Energy insufficient for
any operations
Ready LED: off Ready
contact: opened Not ready
contact: closed
Ready LED: off
Ready contact: opened
Not ready contact: closed
Close Coil continuity not right
Ready LED: blinking Ready
contact: closed Not ready
contact: opened
Ready LED: off
Ready contact: opened
Not ready contact: closed
Open Coil continuity not right
Ready LED: off
Ready contact: opened
Not ready contact: closed
Ready LED: off
Ready contact: opened
Not ready contact: closed
Apx Table 4 Circuit Breaker Condition vs. Position