Binary input/output
module and mA
input module
Ordering no #10 Notes and rules
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1 BIM required in position P3 and 1 BOM required in position P4. Products B30 and C30 require an extra BIM in position P5.
Slot position (front
view/rear view)
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
P14/X141
P15/X151
P16/X161
1/2 case with 1 TRM █ █ █ These black marks
indicate the maximum
number of modules per
casing type and the
slots that can be
occupied.
3/4 case with 1 TRM █ █ █ █ █ █ █ █
3/4 case with 2 TRM █ █ █ █ █
1/1 case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
Compression
terminals
1MRK002960-KA C
No board in slot X X X X X X X X X X X X
Binary output
module 24 output
relays (BOM)
1MRK000614-AB A A A A A A A A A A A A A Maximum 4 (BOM+SOM
+MIM) boards. P5 not in
B30/C30.
BIM 16 inputs,
RL24, 24-30VDC,
50mA
1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
BIM 16 inputs,
RL48, 48-60VDC,
50mA
1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
BIM 16 inputs,
RL110,
110-125VDC,
50mA
1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
BIM 16 inputs,
RL220,
220-250VDC,
50mA
1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
BIM 16 inputs,
RL220,
220-250VDC,
120mA
1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
BIM 16 inputs,
RL24, 24-30VDC,
50mA, enhanced
pulse counting
1MRK000508-HA F F F F F F F F F F F F P5 not in B30/C30
BIM 16 inputs,
RL48, 48-60VDC,
50mA, enhanced
pulse counting
1MRK000508-EA G G G G G G G G G G G G
BIM 16 inputs,
RL110,
110-125VDC,
50mA, enhanced
pulse counting
1MRK000508-FA H H H H H H H H H H H H
BIM 16 inputs,
RL220,
220-250VDC,
50mA, enhanced
pulse counting
1MRK000508-GA K K K K K K K K K K K K
IOM 8 inputs, 10+2
outputs, RL24,
24-30VDC, 50mA
1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, 10+2
outputs, RL48,
48-60VDC, 50mA
1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
IOM 8 inputs, 10+2
outputs, RL110,
110-125VDC,
50mA
1MRK000173-BE N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
IOM 8 inputs, 10+2
outputs, RL220,
220-250VDC,
50mA
1MRK000173-CE P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
1MRK 511 404-BEN A
Product version: 2.2.1
130 ABB