Binary input/output
module and mA
input module
Ordering no #10 Notes and rules
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1 BIM required in position P3 and 1 BOM required in position P4. Products B30 and C30 require an extra BIM in position P5.
IOM 8 inputs 10+2
outputs, RL220,
220-250VDC,
110mA
1MRK000173-CF P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
IOM with MOV 8
inputs, 10+2
outputs, RL24,
24-30VDC, 50mA
1MRK000173-GC U U U U U U U U U U U U
IOM with MOV 8
inputs, 10+2
outputs, RL48,
48-60VDC, 50mA
1MRK000173-AD V V V V V V V V V V V V
IOM with MOV 8
inputs, 10+2
outputs, RL110,
110-125VDC,
50mA
1MRK000173-BD W W W W W W W W W W W W
IOM with MOV 8
inputs, 10+2
outputs, RL220,
220-250VDC,
50mA
1MRK000173-CD Y Y Y Y Y Y Y Y Y Y Y Y
mA input module
MIM 6 channels
1MRK000284-AB R R R R R R R R R R R R Maximum 1 MIM in 1/2
case
P5 not in B30/C30
SOM Static output
module, 12
outputs; 6 standard
relays + 6 static
outputs, 48-60VDC
1MRK002614-BA T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 T1 SOM must not to be
placed in the position
nearest to NUM: 1/2
case slot P5, 3/4 case 1
TRM slot P10, 3/4 case
2 TRM slot P7, 1/1 case
2 TRM slot P13.
P5 not in B30/C30
SOM Static output
module, 12
outputs; 6 standard
relays + 6 static
outputs,
110-250VDC
1MRK002614-CA T2 T2 T2 T2 T2 T2 T2 T2 T2 T2 T2
Selection for
position #10
C
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB 131