1. Set RetripMode = Retrip Off.
2. Apply the fault condition, including start of CCRBRF, well above the set current
value.
3. Verify that no re-trip, but back-up trip is achieved after set time.
Checking the re-trip with current check,
RetripMode
=
CB Pos Check
1. Set RetripMode = CB Pos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set current
value.
3. Verify that re-trip is achieved after set time t1 and back-up trip after time t2
4. Apply the fault condition, including the start of CCRBRF, with the current
below the set current value.
5. Verify that no re-trip, and no back-up trip is obtained.
Checking re-trip without current check
1. Set RetripMode = No CBPos Check.
2. Apply the fault condition, including start of CCRBRF, well above the set current
value.
3. Verify that re-trip is achieved after the set time t1, and the back-up trip after time
t2.
4. Apply the fault condition, including start of CCRBRF, with current below set
current value.
5. Verify that re-trip is achieved after set time t1, but no back-up trip is obtained.
10.4.9.5 Verifying the back-up trip mode
In the cases below it is assumed that FunctionMode = Current is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1. Apply the fault condition, including start of CCRBRF, with phase current well
above set value IP>.
2. Interrupt the current, with a margin before back-up trip time, t2. It may be made
at issue of re-trip command.
3. Check that re-trip is achieved, if selected, but no back-up trip is obtained.
The normal mode BuTripMode = 1 out of 3 should have been verified in the tests
above. In applicable cases the modes 1 out of 4 and 2 out of 4 can be checked. Choose
the mode below, which corresponds to the actual case.
Checking the case
BuTripMode
=
1 out of 4
It is assumed that the earth-fault current setting IN> is below phase current setting
IP>.
1MRK 511 360-UEN A Section 10
Testing functionality by secondary injection
Bay control REC670 2.1 IEC 101
Commissioning manual

Table of Contents

Other manuals for ABB rec670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB rec670 and is the answer not in the manual?

ABB rec670 Specifications

General IconGeneral
BrandABB
Modelrec670
CategoryControl Unit
LanguageEnglish

Related product manuals