ABB rec670 - Verifying Instantaneous Back-Up Trip at CB Faulty Condition; Verifying the Case Retripmode = Contact

ABB rec670
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1. Set BuTripMode = 1 out of 4.
2. Apply the fault condition, including start of CCRBRF, with one-phase current
below set IP> but above IN>. The residual earth-fault should then be above set
IN>.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4. Disconnect AC and START input signals.
Checking the case
BuTripMode
=
2 out of 4
The earth-fault current setting IN> may be equal to or below phase-current setting
IP>.
1. Set BuTripMode = 2 out of 4.
2. Apply the fault condition, including start of CCRBRF, with one-phase current
above set IP> and residual (earth fault) above set IN>.
3. Verify that back-up trip is achieved after set time. If selected, re-trip should also
appear.
4. Apply the fault condition, including start of CCRBRF, with at least one-phase
current below set IP> and residual (earth fault) above set IN>. The current may
be arranged by feeding three- (or two-) phase currents with equal phase angle
(I0-component) below IP>, but of such value that the residual (earth fault)
current (3I
0
) will be above set value IN>.
5. Verify that back-up trip is not achieved.
6. Disconnect AC and START input signals.
10.4.9.6 Verifying instantaneous back-up trip at CB faulty condition
Applies in a case where a signal from CB supervision function regarding CB being
faulty and unable to trip is connected to input CBFLT.
1. Repeat the check of back-up trip time. Disconnect current and START input
signals.
2. Activate the input CBFLT. The output CBALARM (CB faulty alarm) should
appear after set time tCBAlarm. Keep the input activated.
3. Apply the fault condition, including start of CCRBRF, with current above set
current value.
4. Verify that back-up trip is obtained without intentional delay, for example
within 20ms from application of start.
10.4.9.7 Verifying the case
RetripMode
=
Contact
It is assumed that re-trip without current check is selected, RetripMode = Contact.
Section 10 1MRK 511 360-UEN A
Testing functionality by secondary injection
102 Bay control REC670 2.1 IEC