Table 246: JAMPTOC Output signals
Name Type Description
OPERATE BOOLEAN Operate
4.1.7.7 Settings
Table 247: JAMPTOC Non group settings
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Start value 0.10...10.00 xIn 0.01 2.50 Start value
Operate delay time 100...120000 ms 10 2000 Operate delay time
Reset delay time 0...60000 ms 1 100 Reset delay time
4.1.7.8 Monitored data
Table 248: JAMPTOC Monitored data
Name Type Values (Range) Unit Description
START BOOLEAN 0=False
1=True
Start
START_DUR FLOAT32 0.00...100.00 % Ratio of start time /
operate time
JAMPTOC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.1.7.9 Technical data
Table 249: JAMPTOC Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the current
measured: f
n
±2 Hz
±1.5% of the set value or ±0.002 x I
n
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1YHT530004D05 D Section 4
Protection functions
615 series 243
Technical Manual