EasyManua.ls Logo

ABB RED615 - Signals

ABB RED615
896 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
"Latched-S": Latched, ON
This mode is a latched function. At the activation of the input signal, the alarm
shows a steady light. After acknowledgement, the alarm disappears.
Activating
signal
LED
Acknow.
GUID-055146B3-780B-43E6-9E06-9FD8D342E881 V1 EN
Figure 13: Operating sequence "Latched-S"
"LatchedAck-F-S": Latched, Flashing-ON
This mode is a latched function. At the activation of the input signal, the alarm
starts flashing. After acknowledgement, the alarm disappears if the signal is not
present and gives a steady light if the signal is present.
GUID-1B1414BD-2535-40FA-9642-8FBA4D19BA4A V1 EN
Figure 14: Operating sequence "LatchedAck-F-S"
3.4.3 Signals
Table 39: Input signals
Name
Type Default Description
OK BOOLEAN 0=False Ok input for LED 1
ALARM BOOLEAN 0=False Alarm input for LED 1
RESET BOOLEAN 0=False Reset input for LED 1
OK BOOLEAN 0=False Ok input for LED 2
ALARM BOOLEAN 0=False Alarm input for LED 2
RESET BOOLEAN 0=False Reset input for LED 2
OK BOOLEAN 0=False Ok input for LED 3
ALARM BOOLEAN 0=False Alarm input for LED 3
Table continues on next page
Section 3 1YHT530004D05 D
Basic functions
66 615 series
Technical Manual

Table of Contents

Other manuals for ABB RED615