REF 542plus switchbay protection and control unit
Manual Part 3: Installation and Commissioning
1VTA100004-en DMS,2001-10-04 REF542plus: Installation and Commissioning 51 / 80
Figure 13: Back-light Test Page
2 seconds delay
Back light off
1 second delay
Back light on
2 seconds delay. After the delay time is expired the following next test will be started
automatically:
6.4.1.4 LCD contrast test
The following LCD page is shown
LCD CONTRAST TEST
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxx
2 sec
after
To HMI Tests
Page
From Backlight
Test Page
Figure 14: LCD Contrast Test Page
2 seconds delay
Contrast varied from minimum to maximum (in a total time of 2 seconds) and then re-
stored to previous value
2 seconds delay. After the delay time is expired the HMI Test menu will be displayed
automatically: