ABB REG670 2.0 IEC - Test of the Boundary between Zone 1 and Zone 2, Which Is Defined by the Parameter Reachz1

ABB REG670 2.0 IEC
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Define the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V V
V
V
V
ts t FwdZ
VT s
VT p
= × × = × × =0 9 0 9 11931
0 1
13 8
77 81. .
.
.
.
,
,
,
EQUATION14063 V1 EN (Equation 33)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN (Equation 34)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN (Equation 35)
I
50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN (Equation 36)
I
tfs
= 180º
frequency of I
tfs
= 49.5 Hz
Expected result: start of the protection function and trip in zone 2, when trip conditions
are fulfilled.
12.4.5.3 Test of the boundary between zone 1 and zone 2, which is defined by
the parameter
ReachZ1
The trajectory of the impedance traverses the lens characteristic in
zone 2
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V V
V
V
V
ts t RZ
VT s
VT p
= × × = × × =1 1 1 1 1435
0 1
13 8
11 44
1
. .
.
.
.
,
,
,
EQUATION14065 V1 EN (Equation 37)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN (Equation 38)
1MRK502053-UEN B Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC 131
Commissioning manual