EasyManua.ls Logo

ABB REG670 2.0 IEC - Test of the Point SE (R Rvsr, X Rvsx )

ABB REG670 2.0 IEC
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
I
tfs
= 0 A
State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V V
V
V
V
ts t RZ
VT s
VT p
= × × = × × =0 9 0 9 1435
0 1
13 8
9 36
1
. .
.
.
.
,
,
,
EQUATION14066 V1 EN (Equation 53)
=
=
=V
ForwardX
ForwardR
ts
arctan arctan
.
.
59 33
8 19
82..14°
EQUATION14058 V1 EN (Equation 54)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN (Equation 55)
I
50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN (Equation 56)
I
tfs
= 180º
frequency of I
tfs
= 49.5 Hz
Expected result: start of the protection function and trip in zone 1 when trip
conditions are fulfilled.
12.4.5.4 Test of the point SE (R
RvsR
, X
RvsX
)
The trajectory of the impedance traverses the lens characteristic in
zone 1
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/
OutOfStep(78,Ucos)/OOSPPAM(78,Ucos):1/Outputs to check the available
service values of the function block OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V V
V
V
V
ts t RvsZ
VT s
VT p
= × × = × × =0 9 0 9 5899
0 1
13 8
38 47. .
.
.
.
,
,
,
EQUATION14067 V1 EN
(Equation 57)
1MRK502053-UEN B Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC 135
Commissioning manual

Table of Contents

Related product manuals