Path in the local HMI under Main menu/Configuration/Communication/SLM
configuration/Rear optical LON port
Table 9: ADE Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation
TimerClass Slow
Normal
Fast
-
- Slow Timer class
Path in the local HMI under Main menu/Configuration/Communication/SLM
configuration/Rear optical LON port
Table 10: LON commands
Command Command description
ServicePinMsg Command with confirmation. Transfers the node address to the LON Network Tool.
9.2 Optical budget calculation for serial communication
with LON
Table 11: Example
Distance 1 km
Glass
Distance10 m
Plastic
Maximum attenuation -11 dB - 7 dB
4 dB/km multi mode: 820 nm - 62.5/125 um 4 dB -
0.3 dB/m plastic: 620 nm - 1mm - 3 dB
Margins for installation, aging, and so on 5 dB 2 dB
Losses in connection box, two contacts (0.75 dB/contact) 1.5 dB -
Losses in connection box, two contacts (1dB/contact) - 2 dB
Margin for repair splices (0.5 dB/splice) 0.5 dB -
Maximum total attenuation 11 dB 7 dB
Section 9 1MRK502053-UEN B
Establishing connection and verifying the LON communication
92 Generator protection REG670 2.0 IEC
Commissioning manual