EasyManua.ls Logo

ABB REG670 2.0 IEC - Page 145

ABB REG670 2.0 IEC
268 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
frequency of V
ts
= 50 Hz
I
50s
= 0 A
I
tfs
= 0 A
State 2: main test step.
Define the following three-phase symmetrical quantities (the phase angle is
related to phase L1):
V V
V
V
V
ts t RvsZ
VT s
VT p
= × × = × × =1 1 1 1 5899
0 1
13 8
47 02. .
.
.
.
,
,
,
EQUATION14069 V1 EN (Equation 73)
29.60
arctan 180 arctan 180 90.56
0.29
ts
ReverseX
V
ReverseR
Ð = - ° = - ° = - °
æ ö æ ö
ç ÷ ç ÷
è ø è ø
EQUATION14068 V1 EN (Equation 74)
frequency of V
ts
= 50 Hz
I I
I
I
A
s
CTs
CTp
50 50
10459
1
9000
1 162= × = × = .
EQUATION14059 V1 EN (Equation 75)
I
50s
= 0º
frequency of I
50s
= 50 Hz
It I
I
I
A
fs
CTs
CTp
tf= × = × =10459
1
9000
1 162.
EQUATION14062 V1 EN (Equation 76)
I
tfs
= 180º
frequency of I
tfs
= 50.5 Hz
Expected result: the protection function does not issue either start or trip.
After each test it is possible to download and study the related disturbance recording.
1MRK502053-UEN B Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC 139
Commissioning manual

Table of Contents

Related product manuals