19
Dimensions Chapter 5
Installing the IED
Figure 7: Panel-cut out dimensions for side-by-side flush mounting
Case size
Tolerance
A
±1
B
±1
C
±1
D
±1
E
±1
F
±1
G
±1
6U x 1/2 of 19” 214.0 259.3 240.4 190.5 34.4 13.4 6.4 diam
6U x 3/4 of 19” 326.7 259.3 352.8 190.5 34.4 13.4 6.4 diam
6U x 1/1 of 19” 438.7 259.3 465.1 190.5 34.4 13.4 6.4 diam
xx05000505.vsd
B
A
C
G
D
E
F
Note!
With side-by-side flush mounting installation, only IP class 20 is obtained. To reach the IP class
54 the case-by-case flush mounting is recommended.