2.3.3 Sensors and monitoring functions
2.3.3.1 LD0.ARCSARC1 Fault arc protection stage 1
Table 14: LD0.ARCSARC1 Fault arc protection stage 1
IEC 61850 name SA name Description Values
LD0.ARCSARC11
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC11
.Op.general OPERATE Operate 1=Operate
2.3.3.2 LD0.ARCSARC2 Fault arc protection stage 2
Table 15: LD0.ARCSARC2 Fault arc protection stage 2
IEC 61850 name SA name Description Values
LD0.ARCSARC21
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC21
.Op.general OPERATE Operate 1=Operate
2.3.3.3 LD0.ARCSARC3 Fault arc protection stage 3
Table 16: LD0.ARCSARC3 Fault arc protection stage 3
IEC 61850 name
SA name Description Values
LD0.ARCSARC31
.FADet.stVal ARC_FLT_DET Arc detected 1=Detected
LD0.ARCPTRC31
.Op.general OPERATE Operate 1=Operate
2.3.3.4 LD0.SSCBR1 Circuit-breaker condition monitoring
Table 17: LD0.SSCBR1 Circuit-breaker condition monitoring
IEC 61850 name
SA name Description Values
.APwrAlm.stVal IPOW_ALM Iyt alarm 1=Alarm
.APwrLO.stVal IPOW_LO Iyt lockout 1=Lockout
.CBLifAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm
.ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm
.LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm
.OpnAlm.stVal TRV_T_OP_ALM Cls travel time alarm 1=Alarm
.OpNumAlm.stVal OPR_ALM CB operations alarm 1=Alarm
Table continues on next page
Section 2 1MRS757660 A
DNP3 data mappings
26 RET620
Point List Manual