EasyManua.ls Logo

ABB Relion 620 Series - LD0.RESCMMXU1 Residual Current (1); LD0.RESCMMXU2 Residual Current (2); LD0.VMMXU1 Voltage Measurement; LD0.RESVMMXU1 Residual Voltage (1)

ABB Relion 620 Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.5.4.4 LD0.RESCMMXU1 Residual current (1)
Table 166: LD0.RESCMMXU1 Residual current (1)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.RESCMMXU1
.A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.5 LD0.RESCMMXU2 Residual current (2)
Table 167: LD0.RESCMMXU2 Residual current (2)
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.RESCMMXU2
.A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] R 0,40,0,4000
2.5.4.6 LD0.VMMXU1 Voltage measurement
Table 168: LD0.VMMXU1 Voltage measurement
IEC 61850 name SA name Description Values S Arg 1,2,3,4
LD0.VMMXU1.PhV Phase-to-ground voltage
.phsA.cVal.mag U_DB_A -phsA magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsB.cVal.mag U_DB_B -phsB magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsC.cVal.mag U_DB_C -phsC magnitude
0.00…4.00
[xUn] R 0,4,0,400
LD0.VMMXU1.PPV Phase-to-phase voltage
.phsAB.cVal.mag U_DB_AB -phsAB magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsBC.cVal.mag U_DB_BC -phsBC magnitude
0.00…4.00
[xUn] R 0,4,0,400
.phsCA.cVal.mag U_DB_CA -phsCA magnitude
0.00…4.00
[xUn] R 0,4,0,400
2.5.4.7 LD0.RESVMMXU1 Residual voltage (1)
Table 169: LD0.RESVMMXU1 Residual voltage (1)
IEC 61850 name
SA name Description Values S Arg 1,2,3,4
LD0.RESVMMXU1
.PhV.res.instCVal.mag U0_INST Residual voltage
0.00..4.00
[xUn] R 0,4,0,400
1MRS757660 A Section 2
DNP3 data mappings
RET620 67
Point List Manual

Table of Contents

Other manuals for ABB Relion 620 Series

Related product manuals