IEC 61850 name SA name Description Values
.OpNumLO.stVal OPR_LO CB operations lockout 1=Lockout
.PresAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
.PresLO.stVal PRES_LO Low pressure lockout 1=Lockout
.SprChaAlm.stVal SPR_CHR_ALM Spring charge time alarm 1=Alarm
2.3.3.5 LD0.SSCBR2 Circuit-breaker condition monitoring
Table 18: LD0.SSCBR2 Circuit-breaker condition monitoring
IEC 61850 name SA name Description Values
.APwrAlm.stVal IPOW_ALM Iyt alarm 1=Alarm
.APwrLO.stVal IPOW_LO Iyt lockout 1=Lockout
.CBLifAlm.stVal CB_LIFE_ALM CB lifetime alarm 1=Alarm
.ClsAlm.stVal TRV_T_CL_ALM Cls travel time alarm 1=Alarm
.LonTmAlm.stVal MON_ALM CB inactive alarm 1=Alarm
.OpnAlm.stVal TRV_T_OP_ALM Cls travel time alarm 1=Alarm
.OpNumAlm.stVal OPR_ALM CB operations alarm 1=Alarm
.OpNumLO.stVal OPR_LO CB operations lockout 1=Lockout
.PresAlm.stVal PRES_ALM Low pressure alarm 1=Alarm
.PresLO.stVal PRES_LO Low pressure lockout 1=Lockout
.SprChaAlm.stVal SPR_CHR_ALM Spring charge time alarm 1=Alarm
2.3.3.6 LD0.TCSSCBR1 Trip circuit supervision (1)
Table 19: LD0.TCSSCBR1 Trip circuit supervision (1)
IEC 61850 name
SA name Description Values
LD0.TCSSCBR1
.CirAlm.stVal ALARM Supervision alarm 1=Alarm
2.3.3.7 LD0.TCSSCBR2 Trip circuit supervision (2)
Table 20: LD0.TCSSCBR2 Trip circuit supervision (2)
IEC 61850 name
SA name Description Values
LD0.TCSSCBR2
.CirAlm.stVal ALARM Supervision alarm 1=Alarm