2.3.8 Protection related functions
2.3.8.1 DR.RDRE1 Disturbance recorder
Table 81: DR.RDRE1 Disturbance recorder
IEC 61850 name SA name Description Values
DR.RDRE1
.RcdMade.stVal DR recording made 1=Made
2.3.8.2 LD0.SECRSYN1 Synchrocheck
Table 82: LD0.SECRSYN1 Synchrocheck
IEC 61850 name SA name Description Values
LD0.SECRSYN1
.SynPrg.stVal SYNC_INPRO Synch in progress 1=In progress
.FailCmd.stVal CMD_FAIL_AL CB close request failed 1=Failed
.FailSyn.stVal CL_FAIL_AL CB close command failed 1=Failed
2.3.8.3 LD0.CCRDIF1 Current circuit failure protection
Table 83: LD0.CCRDIF1 Current circuit failure protection
IEC 61850 name
SA name Description Values
LD0.CCRDIF1
.Alm.stVal FAIL Fail Alarm 1=Alarm
.Op.general ALARM Fail Operate 1=Operate
2.3.8.4 LD0.CCRDIF2 Current circuit failure protection
Table 84: LD0.CCRDIF2 Current circuit failure protection
IEC 61850 name
SA name Description Values
LD0.CCRDIF2
.Alm.stVal FAIL Fail Alarm 1=Alarm
.Op.general ALARM Fail Operate 1=Operate
2.3.8.5 LD0.CTSRCTF1 Current circuit supervision for transformers (1)
Table 85: LD0.CTSRCTF1 Current circuit supervision for transformers (1)
IEC 61850 name
SA name Description Values
CTRL.CTSRCTF1
.Alm.stVal Alarm output 1 = Alarm
.Op.general CT secondary failure 1 = Failure
Section 2 1MRS757660 A
DNP3 data mappings
42 RET620
Point List Manual