2.4.2.5 CTRL.DCCSWI3 Controllable disconnector (3) control
Table 121: CTRL.DCCSWI3 Controllable disconnector (3) control
IEC 61850 name SA name Description Type
CTRL.DCCSWI3
.Pos.Oper.ctlVal - Disconnector control On/Off
2.4.2.6 CTRL.DCCSWI4 Controllable disconnector (4) control
Table 122: CTRL.DCCSWI4 Controllable disconnector (4) control
IEC 61850 name SA name Description Type
CTRL.DCCSWI4
.Pos.Oper.ctlVal - Disconnector control On/Off
2.4.2.7 CTRL.ESCSWI1 Controllable earth switch (1) control
Table 123: CTRL.ESCSWI1 Controllable earth switch (1) control
IEC 61850 name SA name Description Type
CTRL.ESCSWI1
.Pos.Oper.ctlVal - Earth switch control On/Off
2.4.2.8 CTRL.ESCSWI2 Controllable earth switch (2) control
Table 124: CTRL.ESCSWI2 Controllable earth switch (2) control
IEC 61850 name
SA name Description Type
CTRL.ESCSWI2
.Pos.Oper.ctlVal - Earth switch control On/Off
2.4.3 Sensors and monitoring functions
2.4.3.1 LD0.SSCBR1 Reset signals of CB condition monitoring
Table 125: LD0.SSCBR1 Reset signals of CB condition monitoring
IEC 61850 name
SA name Description Type
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy On
.RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter On
.RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm On
.RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm On
Section 2 1MRS757660 A