IEC 61850 name SA name Description Type
.SPCS04.ctlVal - Output 4 control On/Off
.SPCS05.ctlVal - Output 5 control On/Off
.SPCS06.ctlVal - Output 6 control On/Off
.SPCS07.ctlVal - Output 7 control On/Off
.SPCS08.ctlVal - Output 8 control On/Off
.SPCS09.ctlVal - Output 9 control On/Off
.SPCS10.ctlVal - Output 10 control On/Off
.SPCS11.ctlVal - Output 11 control On/Off
.SPCS12.ctlVal - Output 12 control On/Off
.SPCS13.ctlVal - Output 13 control On/Off
.SPCS14.ctlVal - Output 14 control On/Off
.SPCS15.ctlVal - Output 15 control On/Off
.SPCS16.ctlVal - Output 16 control On/Off
2.4.7.3 LD0.SPCGGIO3 Multipurpose binary outputs (3)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local
operation corresponds to "persistent" for remote operation.
Table 137: LD0.SPCGGIO3 Multipurpose binary outputs (3)
IEC 61850 name
SA name Description Type
LD0.SPCGGIO3
.SPCS01.ctlVal - Output 1 control On/Off
.SPCS02.ctlVal - Output 2 control On/Off
.SPCS03.ctlVal - Output 3 control On/Off
.SPCS04.ctlVal - Output 4 control On/Off
.SPCS05.ctlVal - Output 5 control On/Off
.SPCS06.ctlVal - Output 6 control On/Off
.SPCS07.ctlVal - Output 7 control On/Off
.SPCS08.ctlVal - Output 8 control On/Off
.SPCS09.ctlVal - Output 9 control On/Off
.SPCS10.ctlVal - Output 10 control On/Off
.SPCS11.ctlVal - Output 11 control On/Off
.SPCS12.ctlVal - Output 12 control On/Off
.SPCS13.ctlVal - Output 13 control On/Off
.SPCS14.ctlVal - Output 14 control On/Off
.SPCS15.ctlVal - Output 15 control On/Off
.SPCS16.ctlVal - Output 16 control On/Off
Section 2 1MRS757660 A
DNP3 data mappings
58 RET620
Point List Manual