IEC 61850 name SA name Description Values
.Ind5.stVal - X110-Input 5 1/0=ON/OFF
.Ind6.stVal - X110-Input 6 1/0=ON/OFF
.Ind7.stVal - X110-Input 7 1/0=ON/OFF
.Ind8.stVal - X110-Input 8 1/0=ON/OFF
.SPCSO1.stVal - X110-Output 1 1/0=ON/OFF
.SPCSO2.stVal - X110-Output 2 1/0=ON/OFF
.SPCSO3.stVal - X110-Output 3 1/0=ON/OFF
.SPCSO4.stVal - X110-Output 4 1/0=ON/OFF
2.4 Binary outputs
Table 114: Explanations of the binary output table columns
Column name Description
IEC 61850
name
Original IED data object identification. Described in the IEC 61850 format as
Logical Device.Logical Node and thereafter .Data Object.Data Attribute. Logical
Node is the same as the application function block name.
SA name The signal may have a defined label that is visible, for example, in the Application
Configuration tool in PCM600.
Description Short description of the signal. See the technical manual for more information.
Type Output type. Some outputs can only be controlled with value “On”. Writing “Off” to
these points does not affect the function of the output. See the DNP3 control relay
output block parameters.
2.4.1 System functions
2.4.1.1 LD0.LLN0/LPHD1 Reset indications and LEDs, reset device
Table 115: LD0.LLN0/LPHD1 Reset indications and LEDs, reset device
IEC 61850 name
SA name Description Type
LD0.LLN0
.LEDRs1.Oper.ctlVal - Reset indications and LEDs On
.LEDRs2.Oper.ctlVal - Reset alarm LEDs On
LD0.LPHD1
.RsDev.Oper.ctlVal - Reset device On
Section 2 1MRS757660 A
DNP3 data mappings
52 RET620