Residual current Io and residual voltage Uo
FEEDER
FEEDER MEAS
Iov
Fault
Point
K
R
e
-0.3
-0.2
-0.1
Residual Current (kA)
Residual Voltage x 10
2
(kV)
INCOMER
COMP. COIL
Ioj
Uo
K
R
e
0
0.1
Ioj
(Faulty
Feeder)
Iov
(Healthy
Feeder)
Uo
Pulse width
400 - 800
s
Pulse interval
5 - 300 ms
Peak value
~0.1 ... 5 kA
U
tres
U
tres
I
ctot
R
f
GUID-415078AD-21B3-4103-9622-712BB88F274A V2 EN
Figure 153: Typical intermittent earth-fault characteristics
Earth-fault transients
In general, earth faults generate transients in currents and voltages. There are
several factors that affect the magnitude and frequency of these transients, such as
the fault moment on the voltage wave, fault location, fault resistance and the
parameters of the feeders and the supplying transformers. In the fault initiation, the
voltage of the faulty phase decreases and the corresponding capacitance is
discharged to earth (→ discharge transients). At the same time, the voltages of the
healthy phases increase and the related capacitances are charged (→ charge transient).
If the fault is permanent (non-transient) in nature, only the initial fault transient in
current and voltage can be measured, whereas the intermittent fault creates
repetitive transients.
Section 4 1YHT530004D05 D
Protection functions
308 615 series
Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REM615 A and is the answer not in the manual?

ABB REM615 A Specifications

General IconGeneral
TypeFeeder Protection Relay
Rated Frequency50/60 Hz
Rated Current1 A / 5 A
Communication ProtocolsIEC 61850, Modbus, DNP3
Product Type IDREM615
Protection FunctionsOvercurrent, Earth Fault, Thermal Overload
Operating Temperature-25 to +55 °C
Product NameREM615 A
Rated Voltage100-240 V AC/DC
Number of Binary Outputs6
Input Voltage24-250 V DC
EnclosureIP54
Weight2.5 kg
MountingFlush mounting