Signals
Table 125: T_POS_CL Input signals
Name Type Default Description
POS Double binary 0 Input signal
Table 126: T_POS_OP Input signals
Name Type Default Description
POS Double binary 0 Input signal
Table 127: T_POS_OK Input signals
Name Type Default Description
POS Double binary 0 Input signal
Table 128: T_POS_CL Output signal
Name Type Description
CLOSE BOOLEAN Output signal
Table 129: T_POS_OP Output signal
Name Type Description
OPEN BOOLEAN Output signal
Table 130: T_POS_OK Output signal
Name Type Description
OK BOOLEAN Output signal
Settings
The function does not have any parameters available in LHMI or PCM600.
3.17.1.10 SWITCHR function block
Function block
Figure 73: Function block
Functionality
SWITCHR switching block for REAL data type is operated by the CTL_SW input,
selects the output value OUT between the IN1 and IN2 inputs.
1MRS758755 C
Basic functions
REC615 & RER615
Technical Manual
141