9.2.8 Monitored data
9.2.8.1 DCSXSWI Monitored data
Table 669: DCSXSWI Monitored data
Name Type Values (Range) Unit Description
POSITION Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
9.2.8.2 ESSXSWI Monitored data
Table 670: ESSXSWI Monitored data
Name Type Values (Range) Unit Description
POSITION Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus posi-
tion indication
9.2.9 Technical revision history
Table 671: DCSXSWI Technical revision history
Technical revision Change
B
Maximum and default values changed to 60 s
and 30 s respectively for
Event delay
settings.
C
Outputs OPENPOS and CLOSEPOS are forced
to “FALSE” in case status is Faulty (11).
Table 672: ESSXSWI Technical revision history
Technical revision Change
B
Maximum and default values changed to 60 s
and 30 s respectively for
Event delay
settings.
C
Outputs OPENPOS and CLOSEPOS are forced
to “FALSE” in case status is Faulty (11).
Control functions 1MRS758755 C
642 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB RER615

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RER615 and is the answer not in the manual?

ABB RER615 Specifications

General IconGeneral
BrandABB
ModelRER615
CategoryRelays
LanguageEnglish

Related product manuals