14.5 Energizing inputs of SIM0002/SIM0904
Table 755: Energizing inputs of SIM0002/SIM0904
Description Value
Current sensor in-
put
Rated current voltage (in secon-
dary side)
75 mV...9000 mV
1
Continuous voltage withstand 125 V
Input impedance at 50/60 Hz 2...3 MΩ
2
Voltage sensor in-
put
Rated voltage 6 kV...30 kV
3
Continuous voltage withstand 50 V
Input impedance at 50/60 Hz 3 MΩ
14.6 Binary inputs
Table 756: Binary inputs
Description
Value
Operating range ±20% of the rated voltage
Rated voltage 24...250 V DC
Current drain 1.6...1.9 mA
Power consumption 31.0...570.0 mW
Threshold voltage 16...176 V DC
Reaction time 3 ms
1
Equals the current range of 40...4000 A with a 80 A, 3 mV/Hz Rogowski
2
Depending on the used nominal current (hardware gain)
3
This range is covered (up to 2*rated) with sensor division ratio of 10 000:1
1MRS758755 C Technical data
REC615 & RER615
Technical Manual
853