Parameter Values (Range) Unit Step Default Description
Dead line value 0.1...0.8 xUn 0.1 0.2 Voltage low limit
line for energizing
check
Live line value 0.2...1.0 xUn 0.1 0.8 Voltage high limit
line for energizing
check
Dead bus value 0.1...0.8 xUn 0.1 0.2 Voltage low limit
bus for energizing
check
Live bus value 0.2...1.0 xUn 0.1 0.5 Voltage high limit
bus for energizing
check
Max energizing V 0.50...1.15 xUn 0.01 1.05 Maximum voltage
for energizing
Table 678: SECRSYN Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Control mode
1=Continuous
2=Command
1=Continuous Selection of syn-
chro check com-
mand or Continu-
ous control mode
Close pulse 200...60000 ms 10 200 Breaker closing
pulse duration
Phase shift -180...180 deg 1 0 Correction of phase
difference between
measured U_BUS
and U_LINE
Minimum Syn time 0...60000 ms 10 0 Minimum time to
accept synchroniz-
ing
Maximum Syn time 100...6000000 ms 10 2000 Maximum time to
accept synchroniz-
ing
Energizing time 100...60000 ms 10 100 Time delay for en-
ergizing check
Closing time of CB 40...250 ms 10 60 Closing time of the
breaker
Voltage source
switch
0=False
1=True
0=False Voltage source
switch
9.3.8 Monitored data
9.3.8.1 SECRSYN Monitored data
Table 679: SECRSYN Monitored data
Name Type Values (Range) Unit Description
ENERG_STATE Enum
0=Unknown
1=Both Live
2=Live L, Dead B
3=Dead L, Live B
Energization
state of Line and
Bus
Table continues on the next page
Control functions 1MRS758755 C
654 REC615 & RER615
Technical Manual