Table 144: TPGAPC Output signals
Name Type Description
OUT1 BOOLEAN Output 1 status
OUT2 BOOLEAN Output 2 status
Settings
TPGAPC Non group settings (Basic)
Table 145: TPGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Pulse time 0...60000 ms 1 150 Minimum pulse
time
Technical revision history
Table 146: TPGAPC Technical revision history
Technical revision Change
B Outputs now visible in menu
C Internal improvement
3.17.2.2 Minimum pulse timer TPSGAPC
Function block
Figure 79: Function block
Functionality
The Minimum second pulse timer function TPSGAPC contains two independent
timers. The function has a settable pulse length (in seconds). The timers are used
for setting the minimum pulse length for example, the signal outputs. Once the
input is activated, the output is set for a specific duration using the
Pulse time
setting. Both timers use the same setting parameter.
Figure 80: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
Basic functions
1MRS758755 C
146 REC615 & RER615
Technical Manual