Monday
Q
06:0003:00
12:0009:00 18:0015:00
00:0021:00
Set Mon Act hour = 07 hrs
Set Mon Act Min = 15 min
Set Mon Act Dur = 525 min
Figure 87: Example setting values for Output Q activation
3.17.4.6 Signals
Table 158: DTMGAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0=False Block signal for bina-
ry output
FREEZE BOOLEAN 0=False Freeze signal for bina-
ry output
Table 159: DTMGAPC Output signals
Name Type Description
Q BOOLEAN Output status
3.17.4.7 Settings
Table 160: DTMGAPC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Monday Act enable 0=False
1=True
false Activation / deactivation need
on Monday
Monday Act hour 0...23 h 8 Activation hour time for Mon-
day
Monday Act Mn 0...59 min 0 Activation minute time for Mon-
day
Monday off delay 1...1440 min 1 60 Activation duration for Monday
Tuesday Act enable 0=False
1=True
false Activation / deactivation need
on Tuesday
Tuesday Act hour 0...23 h 8 Activation hour time for Tues-
day
Table continues on the next page
Basic functions 1MRS758755 C
152 REC615 & RER615
Technical Manual