Table 221: Port mode settings
Parameter Values (Range) Unit Step Default Description
Port 1 Mode
Off
On
On
Mode selection for rear port(s). If port is not used,
it can be set to “Off”.
Port 2 Mode
Off
On
On Mode selection for rear port(s). If port is not used,
it can be set to “Off”. Port cannot be set to “Off”
when
Redundant mode
is “HSR” or “PRP” and port
is one of the redundant ports (LAN A or LAN B).
Port 3 Mode
Off
On
On Mode selection for rear port(s). If port is not used,
it can be set to “Off”. Port cannot be set to “Off”
when
Redundant mode
is “HSR” or “PRP” and port
is one of the redundant ports (LAN A or LAN B).
3.20.2.5 Monitored data
Monitored data is available in six locations.
• Monitoring> Communication> Ethernet> Activity> CH1LIV
• Monitoring> Communication> Ethernet> Activity> CH2LIV
• Monitoring/> Communication> Ethernet> Activity> CH3LIV
• Monitoring/> Communication> Ethernet> Link statuses> LNK1LIV
• Monitoring> Communication> Ethernet> Link statuses> LNK2LIV
• Monitoring> Communication> Ethernet> Link statuses> LNK3LIV