EasyManua.ls Logo

ABB RER615 - Page 218

ABB RER615
869 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
For a detailed description of the measurement modes, see
Chapter 11.5
Measurement modes
in this manual.
4.1.1.6 Timer characteristics
(F)PHxPTOC supports both DT and IDMT characteristics. The user can select
the timer characteristics with the
Operating curve type
and
Type of reset curve
settings. When the DT characteristic is selected, it is only affected by the
Operate
delay time
and
Reset delay time
settings.
The protection relay provides 55 IDMT characteristics curves, of which seven comply
with the IEEE C37.112 and six with the IEC 60255-3 standard. Two curves follow the
special characteristics of ABB praxis and are referred to as RI and RD. One user
programmable curve can be used if none of the standard curves are applicable. In
addition to this, there are 39 curves for recloser applications. The DT characteristics
can be chosen by selecting the
Operating curve type
values "ANSI Def. Time" or "IEC
Def. Time". The functionality is identical in both cases.
The timer characteristics supported by different stages comply with the list in
the IEC 61850-7-4 specification, indicate the characteristics supported by different
stages:
Table 223: Timer characteristics supported by different stages
Operating curve type (F)PHLPTOC PHHPTOC
(1) ANSI Extremely Inverse x x
(2) ANSI Very Inverse x
(3) ANSI Normal Inverse x x
(4) ANSI Moderately Inverse x
(5) ANSI Definite Time x x
(6) Long Time Extremely In-
verse
x
(7) Long Time Very Inverse x
(8) Long Time Inverse x
(9) IEC Normal Inverse x x
(10) IEC Very Inverse x x
(11) IEC Inverse x
(12) IEC Extremely Inverse x x
(13) IEC Short Time Inverse x
Table continues on the next page
Protection functions 1MRS758755 C
218 REC615 & RER615
Technical Manual

Table of Contents

Other manuals for ABB RER615

Related product manuals