Name Type Description
ST_B BOOLEAN Start phase B
ST_C BOOLEAN Start phase C
4.1.4.7 Settings
Table 298: PHPTUC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Current block value 0.00...0.50 xIn 0.01 0.10 Low current setting to block in-
ternally
Start value 0.01...1.00 xIn 0.01 0.50 Current setting to start
Operate delay time 50...200000 ms 10 2000 Operate delay time
Table 299: PHPTUC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Operation mode 1=Three Phase
2=Single Phase
1=Three Phase Number of phases needed to
start
Table 300: PHPTUC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
4.1.4.8 Monitored data
Table 301: PHPTUC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
PHPTUC Enum 1=on
2=blocked
3=test
4=test/blocked
5=off
Status
Protection functions 1MRS758755 C
276 REC615 & RER615
Technical Manual