Parameter Values (Range) Unit Step Default Description
-38=Recloser Y
(120)
-39=Recloser Z
(134)
Table 315: FEFLPTOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve 1=Immediate
2=Def time reset
3=Inverse reset
1=Immediate Selection of reset
curve type
Table 316: FEFLPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation 1=on
5=off
1=on Operation Off / On
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for
customer program-
mable curve
Table 317: FEFLPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate
time
20...60000 ms 1 20 Minimum operate
time for IDMT
curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Io signal Sel 1=Measured Io
2=Calculated Io
1=Measured Io Selection for used
Io signal
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
287