Parameter Values (Range) Unit Step Default Description
3=Inverse reset
Operation mode
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1=Phase angle Operation criteria
Enable voltage limit
0=False
1=True
1=True Enable voltage limit
Table 354: DEFLPDEF Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Curve parameter A 0.0086...120.0000 1 28.2000 Parameter A for
customer program-
mable curve
Curve parameter B 0.0000...0.7120 1 0.1217 Parameter B for
customer program-
mable curve
Curve parameter C 0.02...2.00 1 2.00 Parameter C for
customer program-
mable curve
Curve parameter D 0.46...30.00 1 29.10 Parameter D for
customer program-
mable curve
Curve parameter E 0.0...1.0 1 1.0 Parameter E for
customer program-
mable curve
Table 355: DEFLPDEF Non group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Minimum operate
time
50...60000 ms 1 50 Minimum operate
time for IDMT
curves
Allow Non Dir
0=False
1=True
0=False Allows prot activa-
tion as non-dir
when dir info is in-
valid
Measurement
mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT Selects used meas-
urement mode
Min operate current 0.005...1.000 xIn 0.001 0.005 Minimum operating
current
Min operate volt-
age
0.01...1.00 xUn 0.01 0.01 Minimum operating
voltage
Correction angle 0.0...10.0 deg 0.1 0.0 Angle correction
Pol reversal
0=False
1=True
0=False Rotate polarizing
quantity
Io signal Sel
1=Measured Io
2=Calculated Io
1=Measured Io Selection for used
Io signal
Table continues on the next page
Protection functions 1MRS758755 C
322 REC615 & RER615
Technical Manual