Figure 202: Operation in “Intermittent EF” mode, Peak counter limit = 3
Blocking logic
There are three operation modes in the blocking functionality. The operation
modes are controlled by the BLOCK input and the global setting Configuration>
System> Blocking mode which selects the blocking mode. The BLOCK input can be
controlled by a binary input, a horizontal communication input or an internal signal
of the protection relay's program. The influence of the BLOCK signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers"
mode, the operation timer is frozen to the prevailing value. In the "Block all" mode,
the whole function is blocked and the timers are reset. In the "Block OPERATE
output" mode, the function operates normally but the OPERATE output is not
activated.
Protection functions
1MRS758755 C
404 REC615 & RER615
Technical Manual