PDNSPTOC Group settings
Table 423: PDNSPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 10...100 % 1 10 Start value
Operate delay time 100...30000 ms 1 100 Operate delay time
Table 424: PDNSPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation
1=on
5=off
1=on Operation Off / On
Table 425: PDNSPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Min phase current 0.05...0.30 xIn 0.01 0.10 Minimum phase
current
4.3.2.8 Monitored data
PDNSPTOC Monitored data
Table 426: PDNSPTOC Monitored data
Name Type Values (Range) Unit Description
START_DUR FLOAT32 0.00...100.00 % Ratio of start
time / operate
time
RATIO_I2_I1 FLOAT32 0.00...999.99 % Measured cur-
rent ratio I2 / I1
PDNSPTOC Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.3.2.9 Technical data
Table 427: PDNSPTOC Technical data
Characteristic
Value
Operation accuracy Depending on the frequency of the measured current: f
n
±2
Hz
±2% of the set value
Start time <70 ms
Reset time Typically 40 ms
Reset ratio Typically 0.96
Table continues on the next page
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
419