4.6.1.6 Signals
Table 496: DPSRDIR Input signals
Name Type Default Description
U
1
REAL 0.0 Positive sequence
voltage
I
1
REAL 0.0 Positive sequence
current
BLOCK BOOLEAN 0=False Block signal for acti-
vating the blocking
mode
Table 497: DPSRDIR Output signals
Name Type Description
RELEASE BOOLEAN Release signal if direction cri-
teria is satisified
DIRECTION Enum Direction information
4.6.1.7 Settings
Table 498: DPSRDIR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Release delay time 0...1000 ms 1 10 Release delay time
Characteristic an-
gle
-179...180 deg 1 60 Characteristic an-
gle
Max forward angle 0...90 deg 1 88 Maximum phase
angle in forward di-
rection
Max reverse angle 0...90 deg 1 88 Maximum phase
angle in reverse di-
rection
Min forward angle 0...90 deg 1 88 Minimum phase an-
gle in forward di-
rection
Min reverse angle 0...90 deg 1 88 Minimum phase an-
gle in reverse direc-
tion
Directional mode 1=Non-directional
2=Forward 3=Re-
verse
2=Forward Directional mode
Table 499: DPSRDIR Non group settings (Basic)
Parameter
Values (Range) Unit Step Default Description
Operation 1=on 1=on Operation Off / On
Table continues on the next page