Parameter Values (Range) Unit Step Default Description
App layer confirm 1=Disable
2=Enable
1=Disable Application layer confirm
mode
App confirm TO 100...65535 ms 1 5000 Application layer confirm
and UR timeout
App layer fragment 50...2048 bytes 1 2048 Application layer frag-
ment size
UR mode 1=Disable
2=Enable
1=Disable Unsolicited responses
mode
UR retries 0...65535 1 3 Unsolicited retries before
switching to UR offline
mode
UR TO 0...65535 ms 1 5000 Unsolicited response
timeout
UR offline interval 0...65535 min 1 15 Unsolicited offline inter-
val
UR Class 1 Min
events
0...999 1 2 Min number of class 1
events to generate UR
UR Class 1 TO 0...65535 ms 1 50 Max holding time for
class 1 events to gener-
ate UR
UR Class 2 Min
events
0...999 1 2 Min number of class 2
events to generate UR
UR Class 2 TO 0...65535 ms 1 50 Max holding time for
class 2 events to gener-
ate UR
UR Class 3 Min
events
0...999 1 2 Min number of class 3
events to generate UR
UR Class 3 TO 0...65535 ms 1 50 Max holding time for
class 3 events to gener-
ate UR
Legacy master UR 1=Disable
2=Enable
1=Disable Legacy DNP master un-
solicited mode support.
When enabled relay does
not send initial unsolici-
ted message.
Legacy master SBO 1=Disable
2=Enable
1=Disable Legacy DNP Master SBO
sequence number relax
enable
Default Var Obj 01 1=1:BI
2=2:BI&status
1=1:BI 1=BI; 2=BI with status.
Default Var Obj 02 1=1:BI event
2=2:BI event&time
2=2:BI event&time 1=BI event; 2=BI event
with time.
Default Var Obj 03 1=1:DBI
2=2:DBI&status
1=1:DBI 1=DBI; 2=DBI with status.
Default Var Obj 04 1=1:DBI event
2=2:DBI event&time
2=2:DBI event&time 1=DBI event; 2=DBI event
with time.
Default Var Obj 20 1=1:32bit Cnt
2=2:16bit Cnt
5=5:32bit Cnt noflag
6=6:16bit Cnt noflag
2=2:16bit Cnt 1=32 bit counter; 2=16 bit
counter; 5=32 bit coun-
ter without flag; 6=16 bit
counter without flag.
Table continues on the next page
1MRS758755 C Basic functions
REC615 & RER615
Technical Manual
55