Parameter Values (Range) Unit Step Default Description
V high limit res 0.00...4.00 xUn 1 0.05 High warning volt-
age limit
V deadband res 100...100000 1 10000 Deadband configu-
ration value for in-
tegral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Table 610: RESVMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement
mode
1=RMS
2=DFT
2=DFT Selects used meas-
urement mode
8.1.7.5 Monitored data
RESVMMXU Monitored data
Table 611: RESVMMXU Monitored data
Name Type Values (Range) Unit Description
Uo-kV FLOAT32 0.00...4.00 xUn Measured residu-
al voltage
BLOCK BOOLEAN
0=False
1=True
Block signal for
all binary out-
puts
HIGH_ALARM BOOLEAN
0=False
1=True
High alarm
HIGH_WARN BOOLEAN
0=False
1=True
High warning
U_INST_RES FLOAT32 0.00...4.00 xUn Residual voltage
Amplitude, mag-
nitude of instan-
taneous value
U_ANGL_RES FLOAT32 -180.00...180.00 deg Residual voltage
angle
U_DB_RES FLOAT32 0.00...4.00 xUn Residual voltage
Amplitude, mag-
nitude of repor-
ted value
U_DMD_RES FLOAT32 0.00...4.00 xUn Demand value of
residual voltage
U_RANGE_RES Enum
0=normal
1=high
2=low
Residual voltage
Amplitude range