Name Type Values (Range) Unit Description
stantaneous val-
ue
U2_ANGL FLOAT32 -180.00...180.00 deg Negative se-
quence voltage
angle
U2_DB FLOAT32 0.00...4.00 xUn Negative se-
quence voltage
amplitude, re-
ported value
U2_RANGE Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Negative se-
quence voltage
amplitude range
U1_INST FLOAT32 0.00...4.00 xUn Positive se-
quence voltage
amplitude, in-
stantaneous val-
ue
U1_ANGL FLOAT32 -180.00...180.00 deg Positive se-
quence voltage
angle
U1_DB FLOAT32 0.00...4.00 xUn Positive se-
quence voltage
amplitude, re-
ported value
U1_RANGE Enum
0=normal
1=high
2=low
3=high-high
4=low-low
Positive se-
quence voltage
amplitude range
U0_INST FLOAT32 0.00...4.00 xUn Zero sequence
voltage ampli-
tude, instantane-
ous value
U0_ANGL FLOAT32 -180.00...180.00 deg Zero sequence
voltage angle
Table continues on the next page