ABB | SACE Emax 2
Overview of Ekip Touch | 4 - Operating features11 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A
4 - Operating features
Introduction
Ekip Touch has been developed and certified to function in specific environmental, electrical and mechanical
conditions; full details are available in the Technical catalog.
The following sections describe the electrical and power supply characteristics that enable Ekip Touch and
the relative electronic accessories to operate correctly.
Electrical characteristics
The Ekip Touch measurement and protection functions described in this document are provided with primary
voltage and current values within the following nominal ranges:
Parameter Rated operating range
Primary current 0,004 ÷ 16 In
(1)
Primary voltage 5 ÷ 690 V AC
(2)
Rated frequency 45 ... 55 Hz (with fn= 50 Hz) / 54 ... 66 Hz (with fn= 60 Hz)
Peak factor Complying with standard IEC 60947-2
(1)
range with reference to each phase; In refers to the rated size defined by the Rating plug installed on the Trip
unit, available in models from 100 A to 6300 A
(2)
rated highest line-to-line voltage connected directly to Trip unit, also to sockets inside the CB; external
transformers must be used for higher voltage values, consult the chapter dedicated to the Measurement
modules
Self-supply
The internal current sensors are able to supply the Trip unit directly; versions Hi-, G, G Hi- are also fitted
with the Measurement enabler with voltage sockets module, which allows the Trip unit to be supplied by the
installation voltages as well:
Parameter Operating limits
Minimum three-phase turn-on current
> 30 A (E1.2-E2-2-E4.2 with Rating Plug < 400 A)
> 80 A (E1.2-E2-2-E4.2 with Rating Plug 400 A)
> 160 A (E6.2)
Minimum three-phase turn-on voltage > 80 V
Auxiliary power supply
Ekip Touch can be connected to an external auxiliary supply source, which is useful when certain functions
such as communication via Local Bus, recording manual operations, certain measurements and the
datalogger must be activated.
The auxiliary supply can be provided by modules from the Ekip Supply range or by direct connection to the
terminal box.
Direct connection must guarantee the following operating conditions:
Parameter Operating limits
Voltage 24 V DC galvanically isolated
Tolerance ±10%
Maximum ripple ±5%
Maximum inrush current @ 24 V 10 A per 5 ms
Maximum rated power @ 24 V 4 W
Connection cable
Insulated with grounding cable (same characteristics as Belden
3105A/B or higher)
IMPORTANT: if connection is direct, the power supply must be galvanically insulated
and provide the insulation characteristics established by standard IEC 60950 (UL
1950) or equivalent.